Kelvinator Air Conditioner Error Codes

Kelvinator Air Conditioner Error Codes Error codes can help you know when your air conditioning system needs to be repaired or isn’t working as it should. Each error code has a meaning to help you understand the problem and what needs to be done to fix it.

Kelvinator Air Conditioner Error Code Solutions

Error CodesProblem
EELoading EEPROM Malfunction
E2Anti-Freeze Protection
E3Refrigeration System Blocked/Gas Leak
E4Compressor High Temp Protection
E5AC-Over Current Protection
E6Communications Fault
E8Anti-High Temperature Protection
F1Sensor, Room Temperature (Indoor)
F2Sensor, Tube Temperature (Indoor)
F3Sensor, Ambient (Outdoor)
F4Sensor, Coil (Outdoor)
F5Sensor, Compressor Discharge (Outdoor)
F6Anti-High Temperature Protection
FHAnti-Freeze Limit, Frequency Drop
H1Defrosting. It is normal. The unit is in defrosting mode and heating will recommence soon.
H3Compressor Overload Protection
H5IPM Protection
H6Fan Stall, Indoor Unit
HCPFC Protection
P1Compressor Rated Frequency-Test State
P2Compressor Maximum Frequency-Test State
P3Compressor Medium Frequency-Test State
PHHigh Voltage Protection
PLLow Voltage Protection
POCompressor Minimum Frequency-Test State
LPIndoor & Outdoor Units Don’t Match
L3Outdoor DC Fan Motor Malfunction
C5Jumper Cap Malfunction
d1Compressor off
d2The air conditioner continues to cool or heat during the demand  response event,but the electrical energy consumed by the air conditioner in a half your period is not more than 50% of the total electrical energy that would be consumed if operating at the rated capacity in a half hour period.
d3The air conditioner continues to cool or heat during the demand response event, but the electrical energy consumed by the air conditioner in a half your period is not more than 75% of the total electrical energy that would be consumed if operating at the rated capacity in a half hour period.
Kelvinator AC Outdoor Error Codes – Green Led, Red Led, Yellow Led Flash

Malfunction Code Table of Outdoor Unit

Malfunction Code Table of Outdoor Unit-E6 Error
Outdoor Error CodesMeaning
E2Freeze Protection
H5IPM protection
E5Overcurrent protection
EEEEPROM reading and writing malfunction
PLLow voltage protection
PHHigh voltage protection
HCPFC overcurrent protection
LPMismatching of models of indoor and outdoor units
F3Malfunction of outdoor ambient temperature sensor
F4Malfunction of outdoor pipe temperature sensor
F5Malfunction of outdoor discharge temperature sensor
E6Communication malfunction
E3Low pressure protection(refrigerant leak)
U7Abnormality of 4-way valve
E8Over-load protection
E4Discharge temperature protection
H3Overload protection
L9Over power protection
Kelvinator AC Troubleshooting

The air conditioner is not user serviceable. Incorrect repair may cause electric shock or fire, so please contact an authorised service center for professional repair. The following checks prior to contact may save you time and money.

Problem: The unit does not operate

Cause: The unit does not operate if it is turned on immediately after it is turned off. This is to protect the unit. You should wait about 3 minutes.

Problem: Odours are emitted

Cause:

  1. Some odours may be emitted from the indoor unit. This is the result of room smells (such as furniture,tobacco,etc.) which have been taken into the air conditioner.
  2. Consult authorised service centre for cleaning if the odours persist.

Problem: “Water flowing” noise

Cause: The swishing noise like water flowing is the refrigerant flowing inside the unit.

Problem: Mist is emitted in COOL mode

Cause: During cooling operation, a thin mist may be seen emitted from the indoor unit due to high room temperature and humidity. After a period of time, the mist will disappear as the decrease of room temperature and humidity decreases.

Problem: Cracking noise

Cause: This is the sound of friction caused by expansion and/or contraction of panel or other parts due to the change of temperature.

Problem: The unit can not be started up

Cause:

  1. Is the power cut off?
  2. Is the power plug loose? (if applicable )
  3. Is the circuit protection device tripped off?
  4. Is voltage higher or lower? (Tested by professionals)
  5. Is the TIMER correctly used?

Problem: Cooling/Heating effect is poor

Cause:

  1. Is temperature setting appropriate?
  2. Is the inlet or outlet blocked?
  3. Is the filter dirty?
  4. Is the window or the door open?
  5. Is low fan speed set?
  6. Are there heat sources in the room?

Problem: Remote control does not transmit signals

Cause:

  1. Check if there is magnetic or electrical interference near the unit that may affecting operation of the remote control. In this case, pull the plug out and reinsert it.
  2. Is the remote control within its operating range or obstructed? Check the condition of the batteries and replace them if necessary.
  3. Check if the remote control is damaged.

Problem: Water leakage of indoor unit

Cause:

  1. The humidity is high.
  2. Condensing water overflows.
  3. Drain hose is loose or obstructed.

Problem: Water leakage of outdoor unit

Cause:

  1. During cooling operation, water condensates around the pipes and connection joints.
  2. During defrosting operation, thawed water flows out.
  3. During heating operation, water on the heat exchanger drips out.

Problem: Noise from indoor unit.

Cause:

  1. The noise emitted when the fan or compressor relay is switched on or off.
  2. When the defrosting operation is started or stopped, there is a sound of refrigerant flowing in the reverse direction.

Problem: Indoor unit can not blow air

Cause:

  1. In HEAT mode, when the temperature of indoor heat exchanger is very low, air flow is stopped in order to prevent cold air. (within 2 minutes)
  2. In HEAT mode, when the outdoor temperature is low or humidity is high, frost will be formed on the outdoor heat exchanger. The unit will defrost automatically and indoor unit will stop blowing air for 3-12 minutes.
  3. During defrosting operation, water or vapour may be emitted.
  4. In DRY mode, the indoor fan will stop blowing air for 3-12 minutes in order to avoid condensing water being vaporised again.

Problem: Moisture on air outlet

Cause: If the unit operates at high humidity for a long time, moisture will be generated on the air outlet grill and then drip off.

Problem: H1-Defrosting

Cause: It is normal. The unit is in defrosting mode and heating will recommence soon.

Problem: E3-Low pressure warning

Cause: Your air conditioner has lost refrigerant. Contact your installer to check for potential leaks.

The pressure in the refrigeration system is low and could result in the unit breaking down. Ask a certified installer to control it. If any one of the following situations occurs, immediately stop all operations, disconnect the power supply, and contact the authorised personnel.

  • There is a harsh sound during operation.
  • Strong odours are emitted during operation.
  • Water is leaking from the unit.
  • The circuit breaker often trips.
  • Water or other liquid is splashed into the unit.
  • Power cord and power plug is overheating.

Leave a Comment