Viessmann Combi Boiler Error Codes Listed below are the common Viessmann fault codes as described by the boiler manufacturer along with a possible cause.
Viessmann Boiler Error Code Solutions
Vitodens 200 Boiler Error Codes
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
02 | Burner control switches to lockout | Safety chain was activated |
04, 05, 06, 08 | Burner control switches to lockout | Fan speed too high/low at start |
07, 09 | Burner control switches to lockout | Basic level of air pressure threshold in standby mode not correct |
0A | Burner control switches to lockout | Fault, fan speed |
0D | Burner control switches to lockout | Reset button pressed repeatedly or while burner is running |
1A, 1B | Burner blocked | Flow sensor 1, 2 faulty |
1F | Burner blocked | Differential flow rate too large |
25 | Boiler operates with high boiler water temperature | Emissions test switch turned to “hand symbol” for 30 minutes already |
26 | Boiler operates with continuous relay test | Setting mode for maximum or minimum rated input active for 30 minutes already |
35 | Boiler does not activate | Reset button (pressed while burner is OFF) with emissions test switch turned to “hand symbol” |
A2 | N/A | KM-BUS fault to Vitocom |
A5 | N/A | Short circuit / open circuit |
Fault Code 0B
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 200 | Burner control switches to lockout. Fan does not idle after auto reset (incorrect fan rpm). | Severe wind conditions in vent system |
Vitodens 100-W | Burner blocked | Insufficient water flow, incorrect flow direction, defective flow switch. |
Fault Code 0C
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 100-W | Burner blocked | Insufficent power supply |
Vitodens 200 | Burner control switches to lockout | Flame signal still present after switching off |
Fault Code 0F
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 222-F | Control mode | Code “0F” is only displayed in the fault history |
Vitotronic 300 / Vitotronic 300-K, with Vitotronic 300 / Vitodens 200-W / Vitocontrol-S, with Vitotronic 100 | Control mode / Controlled operation | Boiler service required |
Vitotronic 200 / 300 | Normal operation | Boiler service required |
Vitocontrol-S, MW1 with Vitotronic 100 / Vitotronic 300-K, MW1S with Vitotronic 100 | Control mode | Maintenance – “0F” is only displayed in the fault history |
Fault Code 10
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 200-W / 222-F / Vitotronic 300 / 200/ 200-H / 050/200-H / 300-K / vitocontrol-S | Boiler operates based on outdoor temperature of 32°F / 0°C | Short circuit – outdoor temperature sensor |
Vitotronic 300-K, MW2S with Vitotronic 100 / Vitodens 100-W (combiPLUS) / 200-w / Vitocontrol-S, WB2B with Vitotronic 100 | Controls as if the outdoor temperature / Constant Mode | Outdoor temperature sensor shorted out |
Error Code 10, 14, F3, and F4
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 200-W / 222-F / Vitotronic 300 / 200/ 200-H / 050/200-H / 300-K / vitocontrol-S | Boiler operates based on outdoor temperature of 32°F | Short circuit – outdoor temperature sensor |
Vitotronic 300-K, MW2S with Vitotronic 100 / Vitodens 100-W (combiPLUS) / 200-w / Vitocontrol-S, WB2B with Vitotronic 100 | Control as if the outdoor temperature is in constant mode | Outdoor temperature sensor shorted out |
Fault Code 18 and D1
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 100 / 200-W / 222-F / Vitotronic 300-K With 100 / Vitocontrol-S | Boiler operates based on outdoor temperature of 32°F / 0°C / Constant Mode | Outdoor temperature sensor cable broken |
Vitotronic / 100 / 200 / 300 / 050/200-H /300-K / Vitocontrol-S, MW1 with Vitotronic 100 | Operates on basis of 32°F / 0°C outdoor temperature | Open circuit – Outdoor temperature sensor |
Vitotronic 200-H / Vitotronic 300-K, MW1B with Vitotronic 300 / Vitotronic 300-K, MW2B with Vitotronic 200 | Controls as if the outdoor temperature | Lead break – Outdoor temperature sensor |
Vitotronic 050/200-H | Activates after 0°C / 32°F outdoor temperature | Cable break – Outdoor temperature sensor |
Vitodens 100-W | Burner in fault mode | DIP switch S2 is set to “ON” |
Fault Code 19
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 300 | Activates after 0°C / 32°F outdoor temperature | Communication fault, wireless outdoor temperature sensor |
Fault Code 20
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S with Vitotronic 100 / Vitotronic 300 / 300-K / 200 / 100 | Stand-alone control unit without supply temperature sensor (possibly supply temperature not high enough) | Short circuit – Common supply temperature sensor |
Vitocontrol-S with Vitotronic 100 / Vitotronic 300-K, with Vitotronic 200 | Vitocontrol-S, controls in a stand-alone manner w/o supply temperature sensor (supply temperature may not be high enough) | Common supply temperature sensor shorted out |
Vitocrossal 300 | Regulates without supply temperature sensor (low-loss header) | Short circuit – System Flow temperature sensor |
Vitodens 200-W / 222-F | Regulates without supply temperature sensor (low-loss header) | Short circuit – System supply temperature sensor |
Vitotronic 050/200-H< / 200 / 200-H / 300 | Mixing valve closed | Short circuit – Supply temperature sensor / mixing valve circuit M1 |
Vitotronic 300-K, with Vitotronic 100 | Vitotronic 300-K, MW1S controls in a stand-alone manner w/o strap-on sensor (supply temperature may not be high enough) | Short circuit – Strap-on temperature sensor |
Vitodens 200-W | Regulates without supply temperature sensor (low-loss header) | System supply temperature sensor shorted out |
Fault Code 21
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 200 / 300 | Operation without influence of return water temperature | Short circuit – Return water temperature sensor |
Error Code 28
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S with Vitotronic 100 | Vitocontrol-S, VD2/CT3/CM2 controls in a stand-alone manner w/o supply temperature sensor (supply temperature may not be high enough) | Open circuit – common supply temperature sensor |
Vitocontrol-S with Vitotronic 100 / Vitotronic 300-K,with Vitotronic 100 | Vitocontrol-S, WB2B controls in a stand-alone manner w/o supply temperature sensor (supply temperature might not be high enough) | Common supply temperature sensor cable broken |
Vitocrossal 300 / Vitodens 200-W / 22-F | Regulates without supply temperature sensor (low-loss header) | System supply temperature sensor cable broken |
Vitotronic 050/200-H | Mixing valve closes | Cable break – Supply temperature sensor |
Vitotronic 050/200-H | Mixing valve is closed | Open circuit – Supply temperature sensor of mixing valve circuit M1 |
Vitotronic 200-H / Vitotronic 200 / 300 | Mixing valve is being closed | Lead break – Supply temperature sensor in heating circuit with mixing valve M1 (heating circuit 1) |
Vitotronic 300 Vitotronic / 300-K with Vitotronic 300 / 200 | Stand-alone control unit without supply temperature sensor (possibly supply temperature not high enough) | Lead break, common supply temperature sensor |
Vitotronic 300-K with Vitotronic 100 | Vitotronic 300-K, MW1S controls in a stand-alone manner w/o strap-on sensor (supply temperature may not be high enough) | Open circuit – Strap-on temperature sensor |
Fault Code 29, 41, 49, F80, F81, F83, F88 and F89
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 200 / 300 | Normal operation without influence of return water temperature | Open circuit 1 or 2 – Return water temperature sensor (of mixing valve circuit 1) |
Fault Code 30
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S, with Vitotronic 100 / Vitocrossal 300 / Vitodens 200-W / 222-F / Vitotronic 100 / 200 / 300 | Adjustable high limit burner is started and stopped | Short circuit – Boiler water temperature sensor |
Vitocontrol-S with Vitotronic 100 / Vitodens 100-W (CombiPLUS)/ 200-1 | Burner blocked | Boiler water temperature sensor shorted out |
Fault Code 38
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens – 200-W / 222-F / COMBIPLUS | Burner blocked | Boiler water temperature sensor cable broken |
Vitotronic 100 / 200 / 300 / Vitocontrol-S with Vitotronic 100 | Burner is switched on and off by the adjustable high limit | Open circuit – Boiler temperature sensor |
Vitotronic 300-K with Vitotronic 300 / Vitotronic 300-K with Vitotronic 300 | The burner is started and stopped via a temperature controller | Lead break, boiler water temperature sensor |
Vitodens 100-W | Burner blocked | Boiler water temperature sensor lead broken |
Error Code 40 and 44
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Mixing valve closed | Heating circuit 2 with mixing valve supply short circuit on temperature sensor |
Fault Code 41
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 300 | Operation without accounting for return water temperature | Short circuit – Return water temperature sensor of mixing valve circuit 2 |
Fault Code 48 and 4C
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Mixing valve closes / closed | Heating circuit 2 with mixing valve supply temperature sensor cable broken / open circuit |
Fault Code 50, 51, 58 and 59
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 200-W / 222-F | No DHW heating / Fault with DHW | Short circuit/open circuit – DHW tank temperature sensor or lead break |
Error Code 52
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 300 | Control mode | Short circuit – Supply temperature sensor low-loss header |
Vitodens 100-W CombiPLUS | Burner blocked (with CombiPLUS only) | Flow sensor shorted out (in CombiPLUS) |
Fault Code 55, 56 and 57
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 300-K, with Vitotronic 200 | Control mode | Maintenance or error on Vitotronic 100 of boiler 5-8 |
Fault Code 5A, B7, and B8
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Control mode | Lead break, low-loss header – Supply temperature sensor |
All Viessmann boilers | Burner blocked / control mode | Sensor cable broken |
Error Code 5C, 5D, 5E and 5F
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 300-K with Vitotronic 200 | Control mode | Communication fault, Vitotronic 100 of boiler 5-8 |
Fault Code 60, 68, 70, 78, BD, BE and BF
System Behaviour | Cause of Problem | |||
---|---|---|---|---|
No output reduction | Return control open | Boiler with maximum temperature | Short/open circuit Temperature sensor |
Fault Code 80, 81, 82, 83 and FD
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Burner control unit in a fault state; system cools down; burner control unit locked out | Short circuit – Boiler water temperature sensor, burner control unit |
Error Code 88, 89, and E6
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S with Vitotronic 100 / Vitotronic 300-K with Vitotronic 100 / 200 | Control mode | Communication error |
Fault Code 8C, 8D, 8E and 8F
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 300 | Burner control unit in an error mode | Lead break, boiler water temperature sensor, burner control unit |
Fault code 90, 91, 92, 93, 94, 98, 99, 9A, 9B , 9C, 9E, 9F + AB
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Viessmann boilers | Control mode | Short circuit – Temperature sensor [5] / [6] / [7] / [10] |
Error Code A0, A1, A2, AA, and AC
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 200 | Pump running at maximum speed | Open circuit – Internal BUS connection issue |
Fault Code A3, B0, F1, FE1 and FE2
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocrossal 300 / Vitodens 200-W / 222-F / 300 | Control mode is in factory default setting | Programming unit is faulty |
Fault Code A4
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
222-F | Burner blocked. The venting program automatically starting | Air lock in the internal circulation pump or minimum flow rate not achieved |
Fault Code A7
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S with Vitotronic 100 / Vitotronic 100 / Vitotronic 300-K with Vitotronic 300 | Control mode (stays in factory default setting) | Isolation valve error coding OC:2, OC:3 or OC:4 set, and coding 4E:1 not set |
Error Code A8
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Boilers | Control mode issue | Programming unit communication fault |
Fault Code A9, BA, BB, BC and FE0
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 200 | Boiler cools down | Sensor inputs are not read correctly |
Fault Code AD
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 200 | Setting via service level not possible | Data points are not stored internal error VR20 |
Fault Code B1
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S with Vitotronic 100 / Vitotronic 100 / 200 / 300 / Vitotronic 300-K with Vitotronic 100 | Test mode on emissions | Internal electronics error |
Vitocontrol-S with Vitotronic 100 / Vitodens 200-W | Regulates as if the outside temperature was 32°F | Internal error |
Vitotronic 050/200-H | Control characteristics undefined | Electronics internal error |
Error Code B2
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All viessmann boilers | Control mode | Internal electronics error |
Fault Code B3 and E5
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All boilers | Constant Mode | Invalid hardware recognised |
Fault Code B4
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S with Vitotronic 100 / Vitotronic 100 / 200 / 300 / Vitotronic 300-K with Vitotronic 100 | Emissions test mode | Internal electronics fault |
Vitocontrol-S with Vitotronic 100 / Vitodens 200-W | Regulates as if the outside temperature was 32°F (0°C) | Internal fault |
Vitotronic 050/200-H | Undefined control characteristics | Internal electronics fault |
Fault Code B5
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Control mode | External safety equipment |
Error Code B6
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Control mode | Open circuit – KM bus to solar control unit communication error |
Fault Code B9, ED, F0, FE5, FEC, FED, FEE, FEF, FFD + FFF
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S with Vitotronic 100 / Vitotronic 100 / 300 / Vitotronic 300-K with Vitotronic 300 | Boiler cools down | Error maximum pressure limiter 1 2 |
Fault Code C1
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Burner control unit switches to lockout, this could be due to large line voltage fluctuations | Differential air pressure sensor open circuit |
Fault Code C2-C8, CD-CF, D2-D8, DA-DF, and E0
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Boiler cools down | Fixed high limit has responded or fuse F2 has blown. |
Error code C9, CA and CB
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All viessmann boilers | Boiler drives up to electronic maximum limit | Boiler does not log in at the cascade control unit |
Error code CC and F0
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All viessmann boilers | Burner control unit is in fault mode | Ionisation current too high during calibration – Boiler temperature limiter responded air or blockage in system/pump error |
Fault Code D4
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 300 / Vitotronic 300-K with Vitotronic 300 | ||
Vitodens 200 | Boiler is operating in emergency mode (after 30 mins BUS error) or boiler cools down | Internal bus error or open circuit internal bus connection |
Fault Code D5
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Burner blocked | Flue gas temperature sensor not properly positioned – Check Sensor External pump fitted on system |
Fault Code E1, E7, E8, E9, EA, EB, EC and FF2
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitodens 200-W / 222-F / Vitotronic 300 | Burner in fault mode | Flow rate for heating hot water is too low during calibration / flow switch caused shutdown |
Error Code E2 and E3
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All boilers | Burner in fault mode | Heating water flow rate too low during calibration; flow switch caused shutdown |
Fault Code E4
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitotronic 300, Vitodens 200-W, 222-F, Vitocrossal 300, Vitocontrol-S with Vitotronic 100 | Burner error | Burner start flame signal is too weak or missing |
Fault Code EE and EF
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocontrol-S with Vitotronic 100 / Vitocrossal 300 / Vitodens 200-W / 222-F / Vitotronic 300 | Burner blocked | Faulty air pressure – switch air damper flap is stuck |
Fault Code F5
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All viessmann boilers | Gas pressure switch shows no gas pressure / electrical connection error | Gas shut-off valve closed / gas pressure switch faulty / multiple problems with gas supply |
Fault Code F6, 58, F9, FE1, FE2 and FF6
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Burner in error mode emergency operation | Fan not at standstill / plug-in connection error |
Fault Code FA and FB
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Control mode | Communication fault with boiler |
Error Code FB7, FF4, FF2, FF7, FF8 and FF9
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocrossal 200 | Case A: Burner control unit in a fault state; system cools down; burner control unit locked out. Case B: Type of coding card | Case A: Coding card not inserted in the burner control unit; incorrect or faulty coding card. Case B: Coding card does not match burner control unit. |
Fault Code FC
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Burner in fault mode | Gas valve faulty or faulty modulation valve control; or vent system blocked |
Error Code FE
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
All Viessmann boilers | Burner blocked or in error mode | Strong interference (EMC) field nearby, or faulty main PCB |
Error Code FE4
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocrossal 200 | Burner shuts down | Multiple detection of undervoltage |
Fault Code FFA, FFB and FR
Fault Code | System Behaviour | Cause of Problem |
---|---|---|
Vitocrossal 200 / 400-620 / 186-311 | Fan runs without demand; burner control unit in a fault state | Fan has not stopped; cable [100A] faulty; fan faulty; burner control unit faulty |
Viessmann Error Code F4 EE
Viessmann error code F4 EE means that the condensate pipe has frozen and needs to be thawed. You can thaw out the pipe yourself fairly quickly and easily without the need for an engineer but don’t hesitate to contact one if you do not feel confident enough. .