Hisense Air Conditioner Error Codes Press the high power for 4 times in a row and the trouble codes listed below will be displayed. The Error inquiry should be operate in the stand-by state, keep 5 sec press and hold on the Emergency button, the error code will be displayed in 10 sec, then the indoor unit display will recovery to the original. If two or more malfunction happened, each error code will be displayed alternatively. If the appliance could save information under no power condition, then the error code can be inquired as aforesaid with stand-by
state after power resume.
Hisense Air Conditioner Error Code Solutions
Error Codes | Problem |
---|---|
0 | No trouble |
1 | Outdoor coil temperature sensor in trouble |
2 | Compressor temperature sensor in trouble |
3 | Voltage transformer in trouble |
4 | Current transformer in trouble |
5 | IPM module protection |
6 | Over and under-voltage control |
7 | Communication trouble |
8 | Current overload control |
9 | Maximum current control |
10 | Communication trouble (between outdoor unit and driver unit) |
11 | Outdoor EEPROM in trouble |
13 | Compressor exhaust temperature too high control |
14 | Outdoor ambient temperature sensor in trouble |
15 | Compressor housing temperature control |
16 | Anti-freeze or overload control |
18 | DC compressor fails to start |
19 | DC compressor out of step |
33 | Room temperature sensor in trouble |
34 | Indoor coil temperature sensor in trouble |
35 | Between wire remote controller and indoor unit communication trouble |
36 | Communication between the indoor and outdoor in trouble |
37 | Water overbrimmed the pump |
38 | Indoor EEPROM in trouble |
39 | Indoor fan motor operation abnormal |
40 | Grid protection alarm (cabinet type) |
41 | Detecting failures by zero-crossing |
F0 | Wire remote controller EEPROM failure. Change wire remote controller. |
F1 | Wire remote controller temperature sensor failure. Change wire remote controller. |
F2 | Wire remote controller clock IC failure. Change wire remote controller. |
F3 | Wire remote controller humidity sensor failure. Change wire remote controller. |
FE | Communication between main control board & Wiring remote controller Fault (display on wiring remote controller). |
ER | Communication between main control board &display board Fault. |
Error Code: E2
Content: When the evaporator pipe temperature is higher than 63C, the error code will display
The root cause is may be one of the following:
- It is normally for protection, When the indoor pipe temperature between 53C<T<63C, the outdoor fan motor will stop running. When the indoor coil temperature is higher than 63C, the error code will display. After the indoor pipe temperature is lower than 49C, the air conditioner will restart normally.
- The indoor coil temperature sensor is loose;
- The indoor coil temperature sensor is failure;
- The indoor control board is failure.
Error Code: E4
Content: When the indoor fan speed is lower than 200 rpm, the error code will display
The root cause is may be one of the following:
- There are something block the indoor fan motor;
- The fan motor cord connect loose;
- The fan motor is failure;
- The indoor control board is failure
Error Code: EA
Content: the error code will display when the communication between display board and control board have in trouble
The root cause is may be one of the following:
- The connection between the display board and control board is loose;
- The indoor control board is failure.
- The wiring of the display board is failure.
Display of Error Codes:
When the system stops running,press the “CHECK” and “↑↓” buttons, “SERVICE” and “00” will display,”00” is index ,press “∧”and “∨” button to set the value, the index value is displayed at the timer area .Each index value shows corresponding content,as follows:
Trouble code: 0
Troubles: No trouble
Trouble code: 1
Troubles: Outdoor coil temperature sensor in trouble
Possible Cause:
- Outdoor coil temperature sensor is failure
- Outdoor control board in trouble
Trouble code: 2
Troubles: Compressor discharge temperature sensor in trouble
Possible Cause:
- Compressor discharge sensor is failure
- Outdoor control board in trouble
Trouble code: 5
Troubles: IPM protection
Possible Cause:
- Normal protection
- Outdoor IPM control board is failure in the outdoor control board.
- The compressor is failure.
Trouble code: 6
Troubles: Over and under-voltage control
Possible Cause:
- Voltage of power supply is abnormal.
- Outdoor control board in trouble.
Trouble code: 8
Troubles: Current overload control
Possible Cause:
- Normal protection
- The outdoor control board in trouble.
Trouble code: 9
Troubles: Maximum current control
Possible Cause:
- Normal protection
- The compressor is failure
Trouble code: 11
Troubles: Outdoor EEPROM in trouble
Possible Cause: Outdoor control board in trouble.
Trouble code: 13
Troubles: Compressor exhaust temperature too high control
Possible Cause:
- Heat exchanger and indoor filter were dirty.
- The refrigeration system was stopt.
- Compressor discharge temperature sensor is failure.
Trouble code: 14
Troubles: Outdoor ambient temperature sensor in trouble
Possible Cause:
- Outdoor ambient temperature sensor is failure
- Outdoor control board in trouble
Trouble code: 15
Troubles: Compressor housing temperature protection
Possible Cause:
- Compressor overheat protection sensor is failure
- Outdoor control board in trouble
Trouble code: 16
Troubles: Anti-freeze or overload control
Possible Cause:
- Indoor coil temperature sensor is failure.
- Indoor control board in trouble.
Trouble code: 18
Troubles: Compressor fails to start
Possible Cause:
- Compressor is failture.
- Outdoor IPM control board is failure in the outdoor control board.
Trouble code: 33
Troubles: Room temperature sensor in trouble
Possible Cause:
- Room temperature sensor is failure
- Indoor control board in trouble
Trouble code: 34
Troubles: Indoor coil temperature sensor in trouble
Possible Cause:
- Indoor coil temperature sensor is failure
- Indoor control board in trouble
Trouble code: 35
Troubles: Between wire remote controller and indoor unit communication trouble
Possible Cause:
- Wire remote controller in trouble.
- Indoor control board in trouble.
Trouble code: 36
Troubles: Communication between the indoor and outdoor in trouble
Possible Cause:
- Connection cable isn’t well connect
- Indoor control board in trouble
- Outdoor control board in trouble
Trouble code: 37
Troubles: Water overbrimmed the pump.
Possible Cause: Check the pump
Trouble code: 38
Troubles: Indoor EEPROM in trouble
Possible Cause: Indoor control board in trouble.
Indication on the Indoor Unit
If the compressor fails when it is interrupted, the indoor unit’s LED flashes indicating the specific trouble code. It flashes as many times as the number of the trouble code is.
Times: 1
Troubles: Outdoor coil temperature sensor in trouble
Possible Cause:
- Outdoor coil temperature sensor is failure
- Outdoor control board in trouble
Times: 2
Troubles: Compressor discharge temperature sensor in trouble
Possible Cause:
- Compressor discharge sensor is failure
- Outdoor control board in trouble
Times: 4
Troubles: Current transformer in trouble
Times: 5
Troubles: IPM protection
Possible Cause:
- Normal protection
- Outdoor IPM control board is failure in the outdoor control board.
- The compressor is failure.
Times: 6
Troubles: Over and under-voltage control
Possible Cause:
- Voltage of power supply is abnormal.
- Outdoor control board in trouble.
Times: 8
Troubles: Current overload control
Possible Cause:
- Normal protection
- The outdoor control board in trouble.
Times: 9
Troubles: Maximum current control
Possible Cause:
- Normal protection
- The compressor is failure
Times: 11
Troubles: Outdoor EEPROM in trouble
Possible Cause: Outdoor control board in trouble.
Times: 13
Troubles: Compressor exhaust temperature too high control
Possible Cause:
- Heat exchanger and indoor filter were dirty.
- The refrigeration system was stopt.
- Compressor discharge temperature sensor is failure.
Times: 14
Troubles: Outdoor ambient temperature sensor in trouble
Possible Cause:
- Outdoor ambient temperature sensor is failure
- Outdoor control board in trouble
Times: 15
Troubles: Compressor housing temperature protection
Possible Cause:
- Compressor overheat protection sensor is failure
- Outdoor control board in trouble
Times: 16
Troubles: Anti-freeze or overload control
Possible Cause:
- Indoor coil temperature sensor is failure.
- Indoor control board in trouble.
Times: 18
Troubles: Compressor fails to start
Possible Cause:
- Compressor is failture.
- Outdoor IPM control board is failure in the outdoor control board.
Times: 33
Troubles: Room temperature sensor in trouble
Possible Cause:
- Room temperature sensor is failure
- Indoor control board in trouble
Times: 34
Troubles: Indoor coil temperature sensor in trouble
Possible Cause:
- Indoor coil temperature sensor is failure
- Indoor control board in trouble
Times: 35
Troubles: Between wire remote controller and indoor unit communication trouble
Possible Cause:
- Wire remote controller in trouble.
- Indoor control board in trouble.
Times: 36
Troubles: Communication between the indoor and outdoor in trouble
Possible Cause:
- Connection cable isn’t well connect
- Indoor control board in trouble
- Outdoor control board in trouble
Times: 37
Troubles: Water overbrimmed the pump.
Possible Cause: check the pump
Times: 38
Troubles: Indoor EEPROM in trouble
Possible Cause: Indoor control board in trouble.
Hisense Portable AC Error Codes and Troubleshooting
Before calling for service, please try the suggestions below.
Air conditioner will not operate
- The power supply cord is unplugged; Plug into a grounded 3 prong outlet.
- Time-delay fuse or circuit breaker of the wrong capacity is being used; Replace with a time—delay fuse or circuit breaker of the correct capacity.
- The power supply cord has tripped; Press and release RESET.
- A household fuse has blown, or a circuit breaker has tripped: Replace the fuse, or reset the circuit breaker.
- The On/Off button has not been pressed; Press ON/OFF.
- The local power has failed: Wait for power to be restored.
Air conditioner blows fuses or trips circuit breakers
- Too many appliances are being used on the same circuit; Unplug or relocate appliances that share the same circuit.
- You are trying to restart the air conditioner too soon after turning off air conditioner; Wait at least 3 minutes after turning off air conditioner before trying to restart the air conditioner.
Air conditioner power supply cord trips (Reset button pops out)
- Disturbances in your electrical current can trip (Reset button will pop out) the power supply cord; Press and release RESET (listen for click; Reset button will latch and remain in) to resume operation.
- Electrical overloading, overheating, cord pinching or aging can trip (Reset button will pop out) the power supply cord; After correcting the problem, press and release RESET (listen for click; Reset button will latch and remain in) to to resume operation. If the power cord fails to reset, contact a service technician.
NOTE: A damaged power supply cord must be replaced with a new power supply cord obtained from the product manufacturer and must not be repaired.
Air conditioner seems to run too much
- Is there a door or window open? ; Keep doors and windows closed.
- The current air conditioner replaced an older model; The use of more efficient components may cause the air conditioner to run longer than an older model, but the total energy consumption will be less. Newer air conditioners do not emit the ” blast” of cold air you may be accustomed to from older units, but this is not an indication of lesser cooling capacity or efficiency. Refer to the efficiency rating (EER) and capacity rating (in Btu/h) marked on the air conditioner.
- The air conditioner is in a heavily occupied room, or heatproducing appliances are in use in the room; Use exhaust vent fans while cooking or bathing and try not to use heat-producing appliances during the hottest part of the day. Portable air conditioners are designed as supplemental cooling to local areas within a room. A higher capacity air conditioner may be required, depending on the size of the room being cooled.
- Air conditioner runs for a short time only, but room is not cool; Set temperature is close to room temperature; Lower set temperature. See ” portable Air Conditioner Use
Display error code
- If the unit displays error code E5, the water container is full. Drain the water, see “Draining the air conditioner”. After draining, the unit can be operated again.
Air conditioner runs. but does not cool
- The filter is dirty or obstructed by debris; Clean the filter.
- Air outlet is blocked; Clear air outlet.
- Set temperature is too high; Lower set temperature.
Air conditioner cycles on and off too much
- The air conditioner is not properly sized for your room; Check the cooling capabilities of your portable air conditioner. Portable air conditioners are designed as supplemental cooling to local areas within a room.
- The filter is dirty or obstructed by debris; Clean the filter.
- There is excessive heat or moisture, open container cooking, showers,etc. in the room. Use afan to exhaust heat or moisture from the room; Try not to use heat-producing appliances during the hottest part of the day.
- The louvers are blocked; Install the air conditioner in a location where the louvers are free from curtains, blinds, furniture, etc.
Hisense Air Conditioner Troubleshooting
The following cases may not always be a malfunction, please check it before asking for service.
Trouble: Does not run
Analysis:
- If the protector trip or fuse is blown.
- If the plug is not properly plugged.
- If batteries in the remote controller exhausted.
- Please wait for 3 minutes and start again, protector device may be preventing unit to work
Trouble: No cooling or heating air
Analysis:
- Is the air filter dirty?
- Are the intakes and outlets of the air conditioner blocked?
- Is the temperature set properly?
Trouble: Ineffective control
Analysis: If strong interference(from excessive static electricity discharge, power supply voltage abnormality presents, operation will be abnormal. At this time, disconnect from the power supply and connect back 2-3 seconds later.
Trouble: Does not operate immediately
Analysis: Changing mode during operation, 3 minutes will delay.
Trouble: Peculiar odor
Analysis: This odor may come from another source such as furniture, cigarette etc, which is sucked in the unit and blows out with the air.
Trouble: A sound of flowing water
Analysis:
- Caused by the flow of refrigerant in the air conditioner, not a trouble.
- Defrosting sound in heating mode
Trouble: Cracking sound is heard
Analysis: The sound may be generated by the expansion or contraction of the front panel due to change of temperature.
Trouble: Spray mist from the outlet
Analysis: Mist appears when the room air becomes very cold because of cool air discharged from indoor unit during COOLING or DRY operation mode.
Trouble: The compressor indicator(red) lights on constantly, and indoor fan stops.
Analysis: The unit is shifting from heating mode to defrost. The indicator will lights off within ten minutes and returns to heating mode.